SURGE PROTECTION

Power surges caused by lightning, switching events and disturbances within the electrical network can damage sensitive equipment, disrupt operations and result in costly downtime.

PPI supplies a comprehensive range of nVent ERICO surge protection devices (SPDs) designed to protect electrical and electronic systems from transient overvoltages. Solutions are available for protection at the main switchboard, distribution boards and individual sensitive equipment, allowing a coordinated approach to surge protection throughout a facility.

AS 1768 – When is surge protection required?

When there is a threat from lightning, surge protection is considered to be a more important protection measure than external lightning protection.

Surge protection shall be installed:

  • Where the risk assessment deems it necessary
    • a spreadsheet tool is provided with the AS 1768 standard which indicates SPDs required at point of entry (for all service cables) or on all equipment, or both.
  • Where the facility is to be protected from direct lightning strikes
    • that is, when an external lightning protection system is to be installed (contact our office for Lightning Protection solutions)

Surge protection should be installed where the:

  • lightning flash density (Ng) > 2 flashes/km2/year and the conductive services are overhead;
  • consequences of surge damage could affect human safety;
  • consequences of surge damage could affect public service utilities;
  • economic consequences of surge damage are intolerable;
  • where there is a history of surge damage.

If you can’t find your specific product requirement, please call us on 07 3734 7159, or send an email to sales@ppindustries.com.au

Request quote

SURGE PROTECTION SELECTION GUIDE

Installation LocationConnection TypeApplicationERICO Part NumberBrief SpecificationBenefits
Main Switch Board3-PhasePrimary protection device. Large facilities or small facilities where risk is high.DTX120F400TT3-Phase, Imax=120kA, Iimp=17.5kA, Up=1200V@20kA, Uc=300V, IEC Class I, Filtering -29dB@100kHzModular, IEC Class I, Class II, Panel or outside mount, very high 50Hz withstand, indication for power/phase loss and SPD health, RS-485 interface, 10-Year warranty
Main Switch Board3-PhasePrimary protection device. Small facilities where risk is high and there is limited space in SWB.DT1M27530R3-Phase, Imax=65kA, Iimp=25kA, Up=1550V@3kA, Uc=275V, Uf=442V, IEC Class IIEC Class I, Class II, modular, very large surge current rating in small enclosure, alarm contacts, locking modules, universally coordinates with any secondary device in small switchboard.
Main Switch Board1-PhasePrimary protection device. Small facilities where risk is high and there is limited space in SWB.DT1M27510R1-Phase, Imax=65kA, Iimp=25kA, Up=1550V@3kA, Uc=275V, Uf=442V, IEC Class IIEC Class I, Class II, modular, very large surge current rating in small enclosure, alarm contacts, locking modules, universally coordinates with any secondary device in small switchboard.
Main Switch Board3-PhasePrimary protection device. Small facilities where the risk is low.EDT230030R3-Phase, Imax=50kA, In=20kA, Up=1650V, Uc=300V, Uf=442V, IEC Class IITD Technology, Tested to IEC61643 Class II, UL1449-Ed 4, Modular, Locking Modules
Main Switch Board1-PhasePrimary protection device. Small facilities where the risk is low.EDT230010R1-Phase, Imax=50kA, In=20kA, Up=1650V, Uc=300V, Uf=442V, IEC Class IITD Technology, Tested to IEC61643 Class II, UL1449-Ed 4, Modular, Locking Modules
Distribution Board3-PhaseSecondary protection device.EDT230031R3-Phase, Imax=50kA, In=20kA, Up=1650V, Uc=300V, Uf=442V, IEC Class IITD Technology, Tested to IEC61643 Class II, UL1449-Ed 4, Modular, Locking Modules
Distribution Board1-PhaseSecondary protection device.EDT230011R1-Phase, Imax=50kA, In=20kA, Up=1650V, Uc=300V, Uf=442V, IEC Class IITD Technology, Tested to IEC61643 Class II, UL1449-Ed 4, Modular, Locking Modules
Distribution Board or Sub-Panel1-Phase, Series FilterSingle-phase power feeds to sensitive or critical equipment including security and fire panels where the load current is less than 20 Amps, 240VAC.TSF20A240VImax=20kA/mode, Up=800V@3kA, Uc=275V, -50dB@100kHz, IEC Class IILow Up, Attenuates lightning frequencies, UL1449-Ed 4, UL1283-Ed 5 EMI Filter, IEC61643-11 Class II, Modular
Distribution Board or Sub-Panel1-Phase, Series FilterSingle-phase power feeds to sensitive or critical equipment including security and fire panels where the load current is less than 6 Amps, 240VAC.TSF6A240VImax=20kA/mode, Up=800V@3kA, Uc=275V, -50dB@100kHz, IEC Class IILow Up, Attenuates lightning frequencies, UL1449-Ed 4, UL1283-Ed 5 EMI Filter, IEC61643-11 Class II, Modular
Distribution Board or Sub-Pane1-Phase, Series FilterSingle-phase power feeds to sensitive or critical equipment including security and fire panels where the load current is less than 6 Amps, 24V.TSF6A24VImax=20kA/mode, Up=330V@3kA, Uc=30V, -50dB@100kHz, IEC Class IILow Up, Attenuates lightning frequencies, UL1449-Ed 4, UL1283-Ed 5 EMI Filter, IEC61643-11 Class II, Modular
MSB or DB1-PhasePower feeds to sensitive or critical equipment including security and fire panels where the load current is greater than 20 Amps.SRF1xxNImax=130kA, Iimp=50kA, Up=185-550 depending on model, Uc=310V, -40dB@100kHz, IEC Class I+IIExtremely rugged product, Effective filtering of lightning frequencies, Very low Up, Uc & dv/dt, IEC61643-11 Class I+II, Modular
MSB or DB3-PhasePower feeds to sensitive or critical equipment including security and fire panels where the load current is greater than 20 Amps.SRF3xxNImax=130kA, Iimp=50kA, Up=185-550 depending on model, Uc=310V, -40dB@100kHz, IEC Class I+IIExtremely rugged product, Effective filtering of lightning frequencies, Very low Up, Uc & dv/dt, IEC61643-11 Class I+II, Modular
Solar InverterDC PowerPrimary protection device. DC Input, 3-Wire.PVT1xxROperating Voltage up to 1,500 VDC, IEC Class I + Class IIRobust and compact, replaceable surge modules, Complies with UL1449 Edition 4 & EN50539-11 Type 1, Type 2
Solar InverterDC PowerSecondary protection device. DC Input, 3-Wire.PVT2xxROperating Voltage up to 1,500 VDC, IEC Class IIRobust and compact, replaceable surge modules, Complies with UL1449 Edition 4 & EN50539-11 Type 1, Type 2
Data & control circuitsSingle PairSignaling and Control Inputs and Outputs of PLC's, 4-20 mA Loops.UTBxxSPImax=20kA, In=50kA, Up=44V@3kA for UTB30SP, IL=2AHigh Imax, Low Up, compact and Modular
Data & control circuitsDual PairSignaling and Control Inputs and Outputs of PLC's, 4-20 mA Loops.UTBxxDPImax=20kA, In=50kA, Up=44V@3kA for UTB30DP, IL=0.8AHigh Imax, Low Up and Modular
Data room, CCTV camera & multiple other locationsRJ45 connectorLocal Area Networks (LAN) such as CAT5, CAT6 & POE, utilised in security, communications/data and fire detection systems.LANRJ45C6PImax=10kA, Up=150V, Uc=50V, IL=1A, Iimp=1kA 10/350High Iimp, Rugged metallic enclosure, Versatile (CAT5,CAT6,POE) in one product, Simple installation - earthed via DIN rail
Local Area Networks (LAN) or antenna systems, etc.Coaxial CablesCoaxial CablesCSP1xxxxxxImax=20kA, 0-3 GHz, multiple connection optionsHigh Imax, Rugged metallic enclosure, CE & UL Certified, Simple installation, Low insertion and return loss

Tell us what you need